24h Timer Switch ATP1006-2
(The time switch timing can be set second.)
1. Function and Scope
24h Timer Switch ATP1006-2 (hereinafter referred
to as “time switch”) is applicable for regularly controlling switch-on and off
of street lamps, advertising light boxes and other equipments in automatic
control circuit with AC frequency of 50Hz, rated control power voltage of 220V
at most and rated working current of 3A at most.
2. Model and Its Meaning: ATP1006-2
3. Normal Operating Condition and
Installation Condition
3.1 Ambient air humidity: -25℃~+40℃, and
the average temperature is no more than +35℃ in 24h.
3.2 Altitude: no more than 2,000m.
3.3 Humidity: the relative air humidity of
the installation site shall be no more than 50% when the maximum temperature is
+40℃, while it can be higher under lower temperature. Special measures shall be
taken for the condensation occasionally formed due to temperature change.
3.4 Pollution level: 3.
3.5 In the medium with no explosion hazard
and no gas that is enough to corrode metal and destroy the insulation and the
place shall not have severe conductive dust.
3.6 In the place where is provided with
anti-snow and anti-rain equipment but not be full of water steam.
3.7 In the place without significant shake,
shock and vibration.
3.8 Installation class: II.
3.9 Transport and Storage Conditions: -25℃
to +55℃.
3.10 Power voltage change scope: 85%~110%
rated voltage.
3.11 Protection grade: IP20.
4 Main Technical Parameters
4.1 Rated control power voltage: AC (50Hz):
220V.
4.2 Conventional thermal current: (Ith)16A.
4.3 Category of the auxiliary circuit:
AC-15.
4.4 Rated working current (Ie): AC-15 220V 3A.
4.5 Timing error: ≤1s/d.
4.6 Time control scope: 1sec~168h.
4.7 Mechanical life: ≥30,000 times.
4.8 Electric endurance: ≥10,000 times.
4.9 Installation method: Device installed,
guide tracked.
4.10 Anti-interference tolerance sees Table
1.
Table
1 Anti-interference Tolerance
Item
Severity
Static
discharge tolerance
8 ×
(1±10%) KV (air discharge)
Electromagnetic
radiation tolerance
Test
field strength 10 × (1±10%) V/m
Fast
transient tolerance
For
power line: 2 × (1±10%)KV,
duration 1min
Surge
(shock) tolerance
For
power line:1 × (1±10%)KV
RF
conduction tolerance
Open
circuit test voltage 10V, frequency scope 150kHz~80MHz
Voltage
sage tolerance
Sag
30% in half a cycle, sag 60% in 5 cycles and 50 cycles, sag 100% in 250
cycles
5 Outline, Installation Dimension and
Wiring Method
5.1 Outside dimension and installation
dimension see Figure 1.
a) ATP1006-2 outside dimension b)ATP1006-2
installation dimension
Figure
1 Outside dimensions and installation dimensions of ATP1006-2
5.2 Wiring method
5.2.1 Direct control method
Power of the controlled appliance is
supplied in single-phase, of which the working current is no more than the
rated value of this switch. Direct control method may be adopted, wiring method
see Figure 2; for light load with great starting current impact, please adopt
AC contactor expansion control method.
5.2.2 Single-phase expansion method
The controlled appliance is power supplied
in single-phase, of which the working current exceeds the rated value of this
switch. Please adopt AC contactor expansion control method, see Figure 3.
5.2.3 Three-phase operating method
Power of the controlled appliance is
supplied in three-phase, so external AC contactor is required hereof.
a) The coil voltage of the controlled
contactor is AC 220C 50Hz, so its wiring method sees
Figure 4;
b) The coil voltage of the controlled contactor is AC 380V 50Hz, so
its wiring method sees
Figure 5.
Figure 2 Direct single-phase controlled
wiring diagram Figure 3 Single-phase expansion controlled wiring
diagram
Figure 4 Three-phase controlled wiring diagram (220V
for contactor coil) Figure 5 Three-phase controlled wiring diagram
(3800V for contactor coil)
6 Setting and Use
This product
panel is set with five buttons, namely “MD (mode)”, “R (recall)”, “ (left)”, “ (-)” and “ (+)”, so it can adjust
correspondingly hour (h), minute (min) and date; if there is some operating
indication, time switch may be controlled manually or automatically.
6.1 Setting process for time switch
parameters (see Figure 6)
Figure 6 Time switch parameters setting process
6.2 Setting processes are as follows:
6.2.1 Press button “MD” for 3s to cancel
the keyboard lockout, so that “LOCK” may disappear, the current “date” flash,
you can adjust the date then, see Figure 7.
Figure
7
6.2.2 Current date and current time
adjustment
6.2.2.1 Press
buttons “” and “” respectively to adjust
date, for example, if it is Tuesday, you can adjust to “Tu”.
6.2.2.2 Press
“MD” to adjust the current time. Press “” to select the adjusted position and press
“” and “” to plus and minus, so
as to adjust the display time to the current time, see Figure 8.
Figure 8
6.2.3 Timing parameters (switch-on/off
time) setting
6.2.3.1 After finish operation 6.2.2, press
“MD” to set the timing parameters, see Figure 9.
Figure
9
6.2.3.2 1ON
(first switch-on) time setting: press “”,
“” and “” respectively to set 1ON
time and date mode, after setting, press “MD” to enter 1OFF (first
switch-off) time and date mode setting, see Figure 10.
Figure 10
6.2.3.3 1OFF (first switch-off)
time and date model setting: set 1OFF time according to steps specified
in 6.2.3.2.
6.2.3.4 Continue
to press “MD”, the screen will display 2ON, 2OFF … 16ON,
16OFF on the left, set switch time and date model of other groups by
referring to the above steps. For redundant time period, please press “R” to
remove the time of other groups, so that the liquid-crystal display will show “”, see Figure 11, and
then, press “R” to recall.
Figure
11
6.2.4 After
setting time of each group, press “” to set the date. By then, the screen will
show Monday to Sunday types and flash, which means the operating time are alike
from Monday to Sunday, press “” and “” to select an operating mode
suitable for the user, see Table 2.
Table
2 Operating Mode
SN
Operating
Mode
Achieved
function
1
MO TU WE
TH FR SA SU
Operating time is the same every day
2
MO
TU WE TH FR
SA
Operating
time is the same from Monday to Saturday
3
MO
TU WE TH FR
Operating time is the same from Monday to
Friday
4
SA
SU
Operating
time is the same on Saturday and Sunday
5
MO
TU WE
Operating
time is the same from Monday to Wednesday
6
TH
FR SA
Operating
time is the same from Thursday to Saturday
7
MO
WE FR
Operating
time is the same on Monday, Wednesday and Friday
8
TU
TH SA
Operating
time is the same on Tuesday, Thursday and Saturday
9
MO
/ TU / WE / TH / FR / SA
/ SU
Operating
time is different every day
6.2.5 After
setting, press “MD” for 5s, enter operation state, the time switch locks
automatically, “LOCK” shows, and see Figure 12.
Figure
12
6.3 After locking the switch, press “MD”
and “” at the same
time to switch manual/automatic status. Continuously press them together, the
screen will show “AUTO OFF”, “ON”, “ON AUTO” and “OFF” successively, see Figure
13. When the circuit shall be on and off temporarily in the process of
operation, the combination buttons can be used to adjust the switch to ON and
OFF; if the time switch shall work automatically according to the set time, the
combination button shall be used to adjust the switch to “ON AUTO”, then the
time switch may work as set, so as to achieve automatic control.
Figure 13
7 Notes
7.1 The switch into the line can only be
connected to AC220V power supply, do not access the other power.
7.2 If you can not achieve automatic control function,Check the lower right corner of the screen (AUTO) is
right shown?
7.3 The internal battery can only provide the
LCD screen display and settings, such as A1, A2 terminal auxiliary power
missed, is unable to drive the relay output..
7.4 If the user find errors in the products,Through short 3, 4 terminal reset,After reset procedures need to set again.
7.5 When the end
of the product life, please recycle work product or its components, for not
recycled parts, please dispose of, to protect our environment.